Product Description
If you need PNP output, please order PNP.
If you need NPN output, please order NPN.
Features
1, New original high quality parts.
2. Compatible with positive control and negative control.
3. Input signal is isolated by optocoupler with strong anti-interference
4.The input terminal is equipped with status indicator for each channel.
5.High quality PCB carrier. Din rail mountable - for width 35 / 32 / 15mm rails.
Technical Parameters:
Tigger signal :24V
Input current: 5-10mA
Output type: non-contact type
Drive component: P/N channel FET
Maximum output current: 6A
Output voltage: DC5-24V
Operating time: 1ms or less
Reset time: 1ms or less
Maximum switching frequency: 2000Hz
Horizontal group installation: standard rail mounting
Instructions:
X1~X7 are the access terminals of the trigger signal.
S/S is the selection terminal for the high and low levels of the trigger signal.
E.g:
When the trigger signal is high, then the S/S terminal should be connected to the negative terminal corresponding to the trigger signal.
Conversely, when the trigger signal is low, the S/S terminal should be connected to the positive pole corresponding to the trigger signal.